  • 模拟量采集模块ASDCM-8A (2).webp
  • 模拟量采集模块ASDCM-8A (4).webp
  • 模拟量采集模块ASDCM-8A (5).webp
  • 模拟量采集模块ASDCM-8A (3).webp
  • 模拟量采集模块ASDCM-8A (1).webp

Analog Data Acquisition Module ASDCM-8A

It is designed for a wide range of voltage and current acquisition systems, supporting independent configuration of multiple measurement ranges. The device operates at a supply voltage of DC 9–32 V, features standard DIN‑rail mounting, and employs opto‑isolation between its communication interface and analog channels. Additionally, the communication interface incorporates electrostatic discharge (ESD) and surge protection.
  • Commodity name: Analog Data Acquisition Module ASDCM-8A

Phone:

Product Details

  • Product Description
  • Performance Overview

    The industrial‑grade isolated analog signal acquisition module complies with the standard MODBUS‑RTU communication protocol. Internally, it features a 16‑bit ADC and an advanced intelligent processor, supporting a wide range of configuration software and PLC systems. It is suitable for various voltage and current acquisition applications and allows independent configuration of multiple measurement ranges. The device operates on a DC input voltage of 9–32 V, mounts on a standard DIN rail, and employs opto‑isolation between its communication interface and analog channels. Additionally, the communication interface incorporates ESD and surge protection.

    Technical Specifications

    1. Input signal:

    • 8-channel AI: Signal ranges include DC 4–20 mA, –20 mA to 20 mA, 0–5 V, –5 V to 5 V, 0–10 V, and –10 V to 10 V, with an accuracy of 0.05%.

    2. Analog signal sampling rate: 15 samples per second (typical value);

    3. Analog Input Impedance:

    • Voltage: 1.1 MΩ;
    • Current: 100 Ω;

    4. Communication Interface:

    • Physical Layer: RS485
    • Baud rate: Default is 9600 bps; it can also be configured to 2400 bps, 4800 bps, 19200 bps, 38400 bps, 57600 bps, or 115200 bps.
    • Protocol: MODBUS-RTU
    • Communication distance: ≤1000m C

    5. Status indicator light:

    • PWR: Power indicator; remains steadily lit when the module is operating normally.
    • TXD: Master station communication status indicator; the light flashes during normal communication.
    • RXD: Device communication status indicator; the light flashes during normal communication.
    • CH1–CH8: Signal status indicator; remains steadily lit when the analog signal exceeds the set range.

    6. Dielectric Strength: 1500 V AC (between the analog input, the RS485 communication interface, and the power supply; leakage current ≤ 1 mA)

    7. Electromagnetic Compatibility: EMC complies with IEC 61326-3-1.

    8. Power Consumption: Less than 1 W when powered by 24 V DC.

    9. Supply voltage range: 9 V DC to 32 V DC

    10. Operating temperature: -20°C to +60°C

Performance Overview

The industrial‑grade isolated analog signal acquisition module complies with the standard MODBUS‑RTU communication protocol. Internally, it features a 16‑bit ADC and an advanced intelligent processor, supporting a wide range of configuration software and PLC systems. It is suitable for various voltage and current acquisition applications and allows independent configuration of multiple measurement ranges. The device operates on a DC input voltage of 9–32 V, mounts on a standard DIN rail, and employs opto‑isolation between its communication interface and analog channels. Additionally, the communication interface incorporates ESD and surge protection.

Technical Specifications

1. Input signal:

  • 8-channel AI: Signal ranges include DC 4–20 mA, –20 mA to 20 mA, 0–5 V, –5 V to 5 V, 0–10 V, and –10 V to 10 V, with an accuracy of 0.05%.

2. Analog signal sampling rate: 15 samples per second (typical value);

3. Analog Input Impedance:

  • Voltage: 1.1 MΩ;
  • Current: 100 Ω;

4. Communication Interface:

  • Physical Layer: RS485
  • Baud rate: Default is 9600 bps; it can also be configured to 2400 bps, 4800 bps, 19200 bps, 38400 bps, 57600 bps, or 115200 bps.
  • Protocol: MODBUS-RTU
  • Communication distance: ≤1000m C

5. Status indicator light:

  • PWR: Power indicator; remains steadily lit when the module is operating normally.
  • TXD: Master station communication status indicator; the light flashes during normal communication.
  • RXD: Device communication status indicator; the light flashes during normal communication.
  • CH1–CH8: Signal status indicator; remains steadily lit when the analog signal exceeds the set range.

6. Dielectric Strength: 1500 V AC (between the analog input, the RS485 communication interface, and the power supply; leakage current ≤ 1 mA)

7. Electromagnetic Compatibility: EMC complies with IEC 61326-3-1.

8. Power Consumption: Less than 1 W when powered by 24 V DC.

9. Supply voltage range: 9 V DC to 32 V DC

10. Operating temperature: -20°C to +60°C

Please feel free to contact us!

Please provide your contact information and details, ensuring that all fields are filled in correctly. We will get in touch with you within 24 hours.