Product Series
Please feel free to contact us!
We look forward to your call and inquiry!
Company Address
No. 90, Weisan Road, Industrial Zone, Wen County, Jiaozuo City, Henan Province
Service Hotline
Sales call
Technical Support
Email box
ASGPT-GD11D
- Commodity name: ASGPT-GD11D
- Input: 2-wire and 3-wire potentiometers, 0 kΩ to 10 kΩ
- Number of channels: Two in, two out
- Output: 0/4–20 mA (supports passive operation),0–10 mA,0/1–5 V,0–10 V
- Power supply mode (both can be centralized power supply): 24VDC
Product Details
- Product Description
-
Product Introduction
Potentiometer transmitter: It accepts a three-wire potentiometer signal and, after isolation and conversion, outputs either a current or voltage signal. This product features built-in online fault self‑diagnosis and allows users to configure the potentiometer’s zero point and full scale, as well as the output signal type and the output behavior in case of signal failure, via a PC or a handheld programmer.
Technical Specifications
- Power supply: 18 VDC to 32 VDC (independent power supply)
- Operating power consumption: ≤0.7 W (24 V, single-channel full-load output); ≤1.3 W (24 V, dual-channel full-load output)
- Input signal: 2-wire or 3-wire potentiometer, 0 kΩ to 10 kΩ
- Output signals: Current: 0–4 to 20 mA (dual-channel, passive support), 0–10 mA; Voltage: 0–1 to 5 V, 0–10 V.
- Permissible load: 0–4 mA: RL ≤ 550 Ω; 0–10 mA: RL ≤ 1.1 kΩ; 0–1 V: RL ≥ 1 MΩ; 0–10 V: RL ≥ 2 MΩ; passive: RL < [(U − 3) / 0.02] Ω, where U is the loop supply voltage.
- Conversion accuracy: 0.1% F.S. (25°C ± 2°C)
- Temperature Drift: 40 ppm/°C
- Response time: ≤500 ms
- Electromagnetic Compatibility: IEC 61326-3-1
- Dielectric Strength: ≥2500 VAC (between input, output, and power supply)
- Insulation resistance: ≥100 MΩ (input/output/power supply)
- Operating temperature: -20°C to +60°C
- Storage temperature: -40°C to +80°C
- Output status: Unless otherwise specified by the user, regardless of the fault condition of the input signal, the output will track changes in the input signal across the full‑scale range (except for open‑circuit conditions, where the output is 0 V/mA); however, the output shall not exceed 110% of the upper limit of the output range. For example, when the output range is 0 mA to 20 mA, the minimum output may be 0 mA, and the maximum shall not exceed 22 mA.
Product Introduction
Potentiometer transmitter: It accepts a three-wire potentiometer signal and, after isolation and conversion, outputs either a current or voltage signal. This product features built-in online fault self‑diagnosis and allows users to configure the potentiometer’s zero point and full scale, as well as the output signal type and the output behavior in case of signal failure, via a PC or a handheld programmer.
Technical Specifications
- Power supply: 18 VDC to 32 VDC (independent power supply)
- Operating power consumption: ≤0.7 W (24 V, single-channel full-load output); ≤1.3 W (24 V, dual-channel full-load output)
- Input signal: 2-wire or 3-wire potentiometer, 0 kΩ to 10 kΩ
- Output signals: Current: 0–4 to 20 mA (dual-channel, passive support), 0–10 mA; Voltage: 0–1 to 5 V, 0–10 V.
- Permissible load: 0–4 mA: RL ≤ 550 Ω; 0–10 mA: RL ≤ 1.1 kΩ; 0–1 V: RL ≥ 1 MΩ; 0–10 V: RL ≥ 2 MΩ; passive: RL < [(U − 3) / 0.02] Ω, where U is the loop supply voltage.
- Conversion accuracy: 0.1% F.S. (25°C ± 2°C)
- Temperature Drift: 40 ppm/°C
- Response time: ≤500 ms
- Electromagnetic Compatibility: IEC 61326-3-1
- Dielectric Strength: ≥2500 VAC (between input, output, and power supply)
- Insulation resistance: ≥100 MΩ (input/output/power supply)
- Operating temperature: -20°C to +60°C
- Storage temperature: -40°C to +80°C
- Output status: Unless otherwise specified by the user, regardless of the fault condition of the input signal, the output will track changes in the input signal across the full‑scale range (except for open‑circuit conditions, where the output is 0 V/mA); however, the output shall not exceed 110% of the upper limit of the output range. For example, when the output range is 0 mA to 20 mA, the minimum output may be 0 mA, and the maximum shall not exceed 22 mA.
Keywords:
Please feel free to contact us!
Please provide your contact information and details, ensuring that all fields are filled in correctly. We will get in touch with you within 24 hours.