  • ASGEXB-G5D12L (4).webp
  • ASGEXB-G5D12L (3).webp
  • ASGEXB-G5D12L (1).webp
  • ASGEXB-G5D12L (2).webp

ASGEXB-G5D12L

  • Commodity name: ASGEXB-G5D12L
  • Input: Wet contact
  • Number of channels: Two in, two out
  • Output: 12V/45mA drive
  • Power supply mode (both can be centralized power supply): Loop-powered

Phone:

Product Details

  • Product Description
  • Product Introduction

    The switch‑type safety barrier uses wet contacts to control the power supply in the safe area, thereby driving intrinsically safe low‑power devices in the hazardous area, such as solenoid valves and audible/visual alarms. This product features loop power supply and electrical isolation between its input and output circuits.

    Technical Specifications

    • Power Supply: 20 VDC to 32 VDC, with reverse polarity protection.
    • Input signal: wet contact
    • 3.5W (24V, dual-channel full-load output)
    • Input signal: Minimum output voltage: 11.25 VDC at 45 mA; Maximum output voltage: 21.5 VDC; Current limit: ≤45 mA.

     

    • Response time: <20ms
    • Electromagnetic Compatibility: IEC 61326-3-1
    • Dielectric strength: ≥2500 VAC (between intrinsically safe side and non‑intrinsically safe side)
    • Insulation resistance: ≥100 MΩ (input/output/power supply)
    • Operating temperature: -20°C to +60°C
    • Storage temperature: -40°C to +80°C
    • Dimensions: 12.7 mm wide × 110 mm high × 118.9 mm deep
    • Application: Installed in hazardous areas, it can be connected to intrinsically safe equipment in Zones 0, 1, and 2; for gas groups IIA, IIB, and IIC; and for temperature classes T1 through T6.

Product Introduction

The switch‑type safety barrier uses wet contacts to control the power supply in the safe area, thereby driving intrinsically safe low‑power devices in the hazardous area, such as solenoid valves and audible/visual alarms. This product features loop power supply and electrical isolation between its input and output circuits.

Technical Specifications

  • Power Supply: 20 VDC to 32 VDC, with reverse polarity protection.
  • Input signal: wet contact
  • 3.5W (24V, dual-channel full-load output)
  • Input signal: Minimum output voltage: 11.25 VDC at 45 mA; Maximum output voltage: 21.5 VDC; Current limit: ≤45 mA.

 

  • Response time: <20ms
  • Electromagnetic Compatibility: IEC 61326-3-1
  • Dielectric strength: ≥2500 VAC (between intrinsically safe side and non‑intrinsically safe side)
  • Insulation resistance: ≥100 MΩ (input/output/power supply)
  • Operating temperature: -20°C to +60°C
  • Storage temperature: -40°C to +80°C
  • Dimensions: 12.7 mm wide × 110 mm high × 118.9 mm deep
  • Application: Installed in hazardous areas, it can be connected to intrinsically safe equipment in Zones 0, 1, and 2; for gas groups IIA, IIB, and IIC; and for temperature classes T1 through T6.